Installation
Electrical installation
4.2.11 Control connections
4-45
L
EDSVS9332S-B EN 3.0
External voltage supply
++
––
132 4
GND1 GND1
X6
X3
1
AIN1AIN2AOUT1 AOUT2
2
3
4
7762
63
242R
3.3nF
100k
100k
100k
100k
1
2
3
4
5
6
––
––
9300VEC027
Fig. 4-24 Connection of the analog input signals for external voltage supply
Terminal assignment
Signal type Function
Bold = Lenze setting (C0005 = 1000)
Level Technical data
X6/1
X6/2
Analog input 1 Differential input master voltage
Main speed setpoint
6
4
2
5
3
1
-10Vto+10V Resolution:
5 mV (11 bits + sign)
Jumper X3
*
Differential input master current
6
4
2
5
3
1
-20 mA to +20 mA Resolution:
20 μA (10 bits + sign)
Jumper X3
*
X6/3
X6/4
Analog input 2 Differential input master voltage
Additional speed setpoint
Jumper X3 has no
influence
-10Vto+10V Resolution:
5 mV (11 bits + sign)
X6/62 Analog output 1 Monitor 1
Actual speed
-10Vto+10V;
max. 2 mA
Resolution:
20 mV (9 bits + sign)
X6/63 Analog output 2 Monitor 2
Torque setpoint
-10Vto+10V;
max. 2 mA
Resolution:
20 mV (9 bits + sign)
X6/7 GND1, reference potential for analog signals
* To reach the jumpers at X3, remove AIF module from X1, if necessary.