Switch/Discrete Inputs Assign Actions to Inputs
Z-Max Advanced Programming & Systems Design Guide rac00-sdg
Revision A:11/2005 Page 77
Relay Assignment
Assign relays and groups to this input just as for other input types.
Contact Closures
Contact closures are switch inputs which instead of having relays or groups assigned
to them, instead have actions assigned to them. Contact closures have two possible
behaviors:
Maintained
: Under this behavior, two actions can be assigned. The first action, Action
1, occurs whenever the input detects an active (on) state. The second action, Action
2, occurs whenever the input detects an inactive (off) state.
Alt Action:
This behavior assigns a toggle function to the input. Only active states are
recognized. Upon a new active state, the input will issue Action 1 if Action 2 was
issued last or Action 2 if Action 1 was issued last.
OccSen: 3 LOCAL
ADD RELAY/GROUP