4. Trial Operation
4-14
4.8.4 FX / RX operation
1) FX Operation (Forward Run Command by Control Terminal)
Apply 0V between AI1 and 5G (for setting by potentiometer, adjust it to Min).
Check the motor speed display in display group shows ”+0.0rpm” after connecting the terminals FX and CM.
Increase AI1 voltage little by little and check the speed is increasing (for setting by potentiometer, turn the pot
to max. smoothly).
To stop the motor, disconnect the FX and CM terminal.
2) RX Operation (Reverse Run Command by Control Terminal)
Apply 0V between AI1 and 5G (for setting by potentiometer, adjust it to Min).
Check the motor speed display in display group shows ”-0.0rpm” after connecting the terminals RX and CM.
Increase AI1 voltage little by little and check the speed is increasing (for setting by potentiometer, turn the pot
to max. smoothly).
To stop the motor, disconnect the RX and CM terminal.
3) T
he cases of abnormal rotation due to the wrong wiring of encoder and/or motor during low speed
(about 100rpm) operation by control terminal.
Command
Rotating
direction
Speed display Torque display Wiring Status
FX Forward +100.0(rpm) Below +10%
RX Reverse -100.0(rpm) Below -10%
Normal
FX Forward -10 ~ -40(rpm) 150%(Torque Limit)
RX Reverse 10 ~ 40(rpm) -150%(Torque Limit)
Encoder wiring
reversed
FX Reverse -10 ~ -40(rpm) 150%(Torque Limit)
RX Forward 10 ~ 40(rpm) -150%(Torque Limit)
Phase V and W
wiring reversed
FX Reverse +100.0(rpm) Below +10%
RX Forward -100.0(rpm) Below -10%
Encoder and Motor
all reversed
z If A and B phase are reversed, be sure to replace A with B phase wire after checking the pulse
encoder wiring.
z If motor wires are reversed, be sure to replace V with W phase wire after checking the motor
output wiring.
z It does not need to change wiring if user changes the setting value of PAR_11(Enc Dir Set) from “A
Phase Lead” to “B Phase Lead”.
z Torque display is on the basis of the no load operation.