4. Trial Operation
4-15
Operation
Example (1)
Speed Setting via Keypad + Run/Stop via Terminal (FX/RX)
[Operation condition]
-. Control mode : Speed control
-. Ref. Speed : 1500[rpm] setting via keypad
-. Accel/Decel time : Accel - 10[sec], Decel - 20[sec]
-. Run/Stop Src : Run/Stop via FX/RX terminal, Control terminal: NPN mode
[Wiring]
R
S
T
G
U
V
W
FX
RX
BX
RST
P1
P2
P3
P4
CM
VREF
AI1
5G
PE
30A
30C
30B
1A
1B
IM
3P
AC
INPUT
S/W
E
GE
Encoder
A+
A-
B+
B-
2A
2B
OC1
EG
P5
P6
P7
AI2
AI3
[Related Function Code]
Step
Parameter setting Code Description
1 RUN/STOP source select FUN_01 Set it to 0 “Terminal 1”.
2 Speed setting method FUN_02 Set it to 1 “Keypad1”.
3 Ref. Speed Setting FUN_12 Set speed command 1500[rpm] via Keypad.
4 Accel/Decel time
FUN_40
FUN_41
Set Accel time to 10 [sec] in FUN_40.
Set Decel time to 20 [sec] in FUN_41.
5 Terminal FX -
Motor starts to rotate in Forward direction at 1500[rpm] with
Accel time 10 [sec] when FX terminal is turned ON.
Motor decelerates to stop with Decel time 20[sec] when FX
terminal is turned OFF.
6 Terminal RX -
When RX terminal is turned ON motor starts to rotate in Reverse
direction at 1500[rpm] with Accel time 10 [sec]. When it is OFF,
motor decelerates to stop with Decel time 20 [sec].