363-206-285 Trouble Clearing: TAP-114
Issue 2, February 2000 Page 2 of 6
DDM-2000 OC-3 MULTIPLEXER
10. Was a problem found in wiring?
If YES, then continue with Step 11.
If NO, then proceed to Step 12.
11. Correct wiring problem and proceed to Step 17.
12. Is fuse blown on 337A BATTERY CHARGER?
If YES, then proceed to Step 16.
If NO, then continue with Step 13.
13. Is BAT DISCHG LED on 337A BATTERY CHARGER lighted?
If YES, then continue with Step 14.
If NO, then proceed to Step 16.
14. Depress and hold HIGH RATE CHG ACTIVATE pushbutton on 337A
BATTERY CHARGER.IsBAT DISCHG LED lighted?
If YES, then continue with Step 15.
If NO, then proceed to Step 16.
15.
NOTE:
HIGH RATE CHG ON LED will remain lighted until batteries reach
approximately –58 volts. If batteries are completely discharged, it may
take approximately one day for HIGH RATE CHG ON LED to go out.
Release HIGH RATE CHG ACTIVATE pushbutton. Does BAT DISCHG LED
go off and is HIGH RATE CHG ON LED lighted?
If YES, then proceed to Step 17.
If NO, then continue with Step 16.
16. Replace 337A BATTERY CHARGER and proceed to Step 17.
17. Did alarm clear?
If YES, then STOP. YOU HAVE COMPLETED THIS PROCEDURE.
If NO, then proceed to Step 23.
18. Use DMM to measure voltage at battery shelf jacks J5 (+BAT)andJ6 (–BAT).

Table of Contents

Other manuals for Lucent Technologies DDM-2000 OC-3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lucent Technologies DDM-2000 OC-3 and is the answer not in the manual?

Lucent Technologies DDM-2000 OC-3 Specifications

General IconGeneral
BrandLucent Technologies
ModelDDM-2000 OC-3
CategoryMultiplexer
LanguageEnglish

Related product manuals