363-206-285 Detailed Level Procedure: DLP-536
Issue 2, February 2000 Page 1 of 4
DDM-2000 OC-3 MULTIPLEXER
PerformTestofRTBatteriesUsing
197A BATTERY LOAD TEST SET
1.
!
CAUTION:
Service interruption will occur if batteries are disconnected and AC power
is not available.
Obtain 197A BATTERY LOAD TEST SET (197A) and place near batteries to
be tested (Figure 1).
Figure 1 – 197A Battery Load Test Set Test Connections