EasyManua.ls Logo

Megger MFT-X1 - Connectivity and Reset Settings

Megger MFT-X1
110 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10.4 Protective earth and touch voltage warnings
When you are carrying out a live circuit test (other than current measurement) and you touch the test button to start
the test, the instrument automatically carries out a protective earth confirmation (PE confirmation) test.
This is not the same as the touch voltage test described in the next section.
For the PE confirmation test, if the instrument detects a difference in potential greater than the touch voltage limit
you have set (25 V or 50 V) between your finger on the TEST button and the PE conductor of the circuit under test, it
will warn you with the following symbol in the display:
either:
(1) inhibit the test
Fig 27: PE warning blocking
(2) allow the test to continue with the warning symbol present
Fig 28: PE warning non-blocking
You can do this in set up – Refer to 15.5.10 PE con󰄈rmation on page 81.
The most common cause for this error is a high resistance or missing earth connection.
To adjust the touch voltage setting Refer to 15.8.2 Maximum touch voltage on page 85.
10.4.1 Protective earth warning (PE) operation
When making a measurement on live circuits the red pad on either of the test buttons should be touched for at least
1 second to allow the PE warning detection to operate.
NOTE : Do not press the test button, just touch it. This is adequate for the detection circuit to identify a
fault without instigating a measurement.
www.megger.com MFT-X1
41
Live circuit tests

Table of Contents

Other manuals for Megger MFT-X1

Related product manuals