EasyManua.ls Logo

Minebea CC-Link CSD-892-73 - Page 48

Minebea CC-Link CSD-892-73
159 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
37
Setting of Function
Reference No. Item Function No. Set value Contents
6-11
Stability detection in the
setting.
CF-20
0 Invalid
1 Valid
6-12-1
Method of setting
gravity acceleration
compensation
CF-25
0 Set the district number
1 Set the numerical value of gravity acceleration
6-12-2
District number of using
place
CF-26
(Can be set in
CF25=0)
01~16 Unit : District
10
6-12-3
District number of
calibration place
CF-27
(Can be set in
CF25=0)
01~
16 Unit : District
10
6-12-4
Gravity acceleration value
setting of using place
CF-28
(Can be set in
CF25=1)
9.000~
9.999
9.797
Unit : m/s
2
6-12-5
Gravity acceleration value
setting of calibration place
CF-29
(Can be set in
CF25=1)
9.000~
9.999
9.797
Unit : m/s
2
6-13
Calibration data
(for reference)
Scale interval
CF-90 At the shipment from factory : 1
6-13
Calibration data
(for reference)
Weighing capacity
CF-9
1 At the shipment from factory : 10000
6-13
Calibration data
(for reference)
mass of weight
CF-92 At the shipment from factory : 10000
6-13
Calibration data
(for reference)
ZERO mV/V value
CF-93 At the shipment from factory : 0.0000
6-13
Calibration data
(for reference)
SPAN mV/V value
CF-94 At the shipment from factory : 0.5000
6-14
Stability detection time
width at calibration
CF-97
00~99
Unit : 0.1 s
00 : OFF of
stability detection at calibration.
05
6-15 Digital linearize clear CF-98
The data of the compensation by the digital
linearization is cleared.
6-16 C function clear CF-99 C function set content is returned default setting.
: default

Table of Contents