36
Setting of Function
5-2. Details of C function data
Reference No. Item Function No. Set value Contents
6-1
Display position of
decimal point
CF-01
0 No decimal point
1 1234.5
2 123.45
3 12.345
4 1.2345
6-2 A/D sampling rate CF-02
0 50 times/s
1 100 times/s
2 250 times/s
3 500 times/s
6-3
Condition of overload
display
CF-03
0 At exceeding | Weighing capacity + 9D |
1 At exceeding 110 % of Weighing capacity
2 At exceeding -20D (Weighing capacity+9D)
6-4
Comparative operation
display
synchronization
CF-04
0 Invalid
1 valid
6-5 Unit CF-05
0 No unit
1 g
2 kg
3 t
4 lb
5 N
6 Pa
7 kN
8 kPa
9 MPa
6-6-1
Operating condition of
ZERO set
CF-10
0 Operation on stable condition
1 Operation by unconditional
6-5-2
Effective range of ZERO
set
CF-11
00 30
Unit : ± 1 % of weighing capacity
00 : ZERO set off
02
6-7-1 Target of ZERO tracking CF-12
0 Gross value and Net value
1 Gross (Only when gross weight displays.)
6-7-2
Date width of ZE
RO
tracking
CF-13
000 999 Unit : 0.1 D
000 000 : ZERO tracking is OFF
6-7-3
Time width of ZERO
tracking
CF-14
00 99 Unit : 0.1 s
00 00 : ZERO tracking is OFF
6-8-1 Operation of power on CF-15
0 Invalid
1 valid
6-9-1
Operating condition of
tare weight cancellation
CF-16
0 in steady by 0 < Gross value <= Weighing capacity
1 in normal by 0 < Gross value <= Weighing capacity
2 in steady by Gross weight <= Weighing capacity
3 in
normal by Gross weight <= Weighing capacity
6-10 Date stored CF-17
000 111
100
0 : Internal RAM
1 : EEPROM
10
0
: Data of ZERO set.
10
1
: Tare weight cancellation
10
2
: Setting mode of simple comparison mode, and
setting data of 5 steps of comparator mode.
: default

Table of Contents