3
SPECIFICATIONS
3.2 Function List
3.2.3 Input signal error detection function
3 - 24
1
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
SETUP AND
PROCEDURES
BEFORE OPERATION
5
UTILITY PACKAGE
(GX CONFIGURATOR-
AD)
6
PROGRAMMING
7
ONLINE MODULE
CHANGE
8
TROUBLESHOOTING
2) To detect input signal errors at an upper limit value only
• Input signal error detection extended setting: 1 (different upper/lower limit
values)
• Input signal error detection upper limit setting value: 100 (10.0%)
• Input signal error detection lower limit setting value: 251 (input signal error
detection disabled)
3) To detect input signal errors at different upper and lower limit values
• Input signal error detection extended setting: 1 (different upper/lower limit
values)
• Input signal error detection upper limit setting value: 50 (5.0%)
• Input signal error detection lower limit setting value: 120 (12.0%)
Input signal error detection
upper limit value
21.6mA
Offset value
20mA
Gain value
4mA
Input signal error detection
lower limit value
Error
No error
detected
1.6mA
(10.0 of 16mA)
1.6mA
(10.0 of 16mA)
16mA
(Gain value - Offset value)
2.4mA
Input signal error detection
upper limit value
20.8mA
Offset value
20mA
Gain value
4mA
Input signal error detection
lower limit value
Error
Error
0.8mA
(5.0 of 16mA)
1.92mA
(12.0 of 16mA)
16mA
(Gain value - Offset value)
2.08mA