3 -  29 
3. SIGNALS AND WIRING 
 
(3) Speed limit 
(a) Speed limit value and speed 
The speed  is  limited  to  the  values set  in parameters No.  PC05  to  PC08  and  PC31  to PC34  (Internal 
speed limit 0 to 7). 
When  the  servo  motor  speed  reaches  the  speed  limit  value,  the  internal  torque  control  may  become 
unstable. Make the set value more than 100r/min greater than the desired speed limit value. 
The following table indicates the limit direction according to forward rotation selection (RS1) and reverse 
rotation selection (RS2) combination. 
 
(Note) Input device 
Speed limit direction 
Forward rotation (CCW)
Reverse rotation (CW)
 
RS1  RS2 
1  0  Forward rotation (CCW) 
0  1  Reverse rotation (CW) 
Note. 0: off 
1: on 
Connect the wirings as follows when setting the internal speed limit to the eighth speed. 
SP2
SP3
DOCOM
DICOM
Servo amplifier
SP1
24VDC
(Note 2)
RS2
RS1
(Note 1)
 
Note 1. For sink I/O interface. For source I/O interface, refer to section 3.8.3. 
2. Set the input devices by parameter No. PD02 to PD14. 
 
POINT 
 
The servo-on (SON), the forward rotation stroke end (LSP), and the reverse 
rotation stroke end (LSN) can be set to turn on automatically by parameter 
No. PD01 (input signal automatic ON selection 1).