(F) When the Peak Cut method [From external system] is selected
(1) In the [Temperature difference between set point and inlet] section, a temperature differential can be set to
between 3 and 9 as necessary. The Peak Cut control setting that corresponds to the control level 0 will be
disregarded for the indoor unit groups in which the temperature difference between the set temperature and
the room temperature is greater than the specified temperature differential.
Note: The Peak Cut control setting that corresponds to the control levels 1 to 4 will be effective regardless of the temperature
differential setting.
Peak Cut method
Temperature difference
between set point and
inlet
Save Settings