72
WT07627X03
Note: For heat pump outdoor units and City Multi S series (PUMY) outdoor units, leave the default setting [100%] as it is not to
activate the capacity-save control.
However, [50%] though [100%] can be set on the following models.
PUMY-P**KM or later
PUMY-P**KM-A or later
PUMY-P**HMC-S or later
PUMY-P**HMC-C or later
PUMY-P**KMC-C or later
PUMY-P**YKM.TH(-T) or later
Note: AE-200/AE-50/EW-50 that support Maximum Capacity [50%] are from Ver. 7.23 or later.
(2) For each control level, set the total time in which the Peak Cut control is performed during every 30 minutes.
Setting the time to [30] minutes is preferable, for shorter control time is not likely to bring much benefit.
If any time other than [30] minutes is selected, the outdoor units will operate in rotation so that they will not
perform the Peak Cut control at the same time.
(3) To copy the settings of an outdoor unit to the settings for other outdoor units, display the outdoor unit whose
settings are to be copied and touch [Copy], then display the outdoor unit to which the copied settings are to be
pasted and touch [Paste]. The rectangular icons next to the selected buttons will appear in yellow-green.