81
WT07627X03
When the External Temperature Interlock function is active, the set temperature will be adjusted as shown
below.
“Cool” and “Dry” modes
29
30
31
32
33
34
35
36
27
28
26
25
24
23
Outdoor temperature conditions Set temperature after being adjusted
Outdoortemperature≥
Set temperature + 1.5°C (3°F)
Set temperature + 1°C (2°F)
Outdoortemperature≥
Set temperature + 4.5°C (9°F)
Set temperature + 2°C (4°F)
Outdoortemperature≥
Set temperature + 6.5°C (12°F)
Set temperature + 3°C (6°F)
Outdoortemperature≥
Set temperature + 7.5°C (14°F)
Set temperature + 4°C (8°F)
“Heat” mode
12
13
14
15
16
17
18
19
10
11
9
8
7
6
Outdoor temperature conditions Set temperature after being adjusted
Outdoortemperature≤
Set temperature - 4.0°C (8°F)
Set temperature - 1°C (2°F)
Outdoortemperature≤
Set temperature - 6.0°C (11°F)
Set temperature - 2°C (4°F)
Outdoortemperature≤
Set temperature - 8.0°C (15°F)
Set temperature - 3°C (6°F)
Outdoortemperature≤
Set temperature - 10.0°C (18°F)
Set temperature - 4°C (8°F)
Temperature (°C)
Outdoor temperature
Time
Set temperature after being adjusted
when [Control levels] is set to [±4°C]
(±8°F)
Set temperature
Temperature (°C)
Set temperature
Set temperature after being adjusted
when [Control levels] is set to [±4°C]
(±8°F)
Time
Outdoor temperature