[8] Output - Check sheet for billing function trial run
Click [Option] > [Output - Check sheet for billing function trial run] in the tool bar to output the check sheet used for
billing function trial runs.
Note: The check sheet will be output based on the settings on the Initial Setting Tool.
If the settings on the AE-200/AE-50/EW-50 and the Initial Setting Tool are not the same, the billing function trial will not run
correctly. Be sure to complete [5] “Send” before starting the trial run.
(1) Click [Option] > [Output - Check sheet for billing function trial run] in the tool bar.
(2) Clickthepull-downmenu(▼)for“Centralizedcontroller”andselectthenumberforthecentralizedcontroller
to be output.
Note: This centralized controller number is the one set in section 6-3-1 “System Configuration settings”.
Note: To output the check sheet for all centralized controllers and all output types at once, select [Batch output] for “Output
target”.
(3) Clickthepull-downmenu(▼)for“Outputtype”andselectthe[Itemstobecheckedduringthetrialrun]for
the first trial run. For the second trial run, select [Items to be checked 10 days after the trial run]. For the
third trial run, select [Items to be checked on the next day of the closing date].
(4) Click [Data Output].
(5) Set the file name and save destination and then click [Save].
Note: Refer to the Instruction Book (Apportioned Electricity Billing Function) for details of the check sheet.
[9] Output - Check sheet for air-conditioner ON/OFF trial run
Click [Option] > [Output - Check sheet for air-conditioner ON/OFF trial run] in the tool bar to output the check sheet
used for air-conditioner ON/OFF trial runs.
Note: The check sheet will be output based on the settings on the Initial Setting Tool.
If the settings on the AE-200/AE-50/EW-50 and the Initial Setting Tool are not the same, the air-conditioner ON/OFF trial will
not run correctly. Be sure to complete [5] “Send” before starting the trial run.
(1) Click [Option] > [Output - Check sheet for air-conditioner ON/OFF trial run] in the tool bar.
(2) Clickthepull-downmenu(▼)for“Centralizedcontroller”andselectthenumberforthecentralizedcontroller
to be output.
Note: This centralized controller number is the one set in section 6-3-1 “System Configuration settings”.
Note: To output the check sheet for all centralized controllers at once, select [Batch output] for “Output target”.
(3) Click [Data Output].
(4) Set the file name and save destination and then click [Save].
Note: Refer to “Appendix 1: Air-conditioner ON/OFF trial run” for the contents of the check sheet.
Note: When the PC with Initial Setting Tool installed and the centralized controller are connected via a LAN, the license
registration status can be output in the check sheet.