9 Visualization
Maschinenfabrik Reinhausen GmbH 2020108 6385142/08 ENETOS
®
ED
9.2.1 Setting general device functions
You can set general device functions with the following parameters.
Parameters
General
Language English
Commissioning wizard Yes
Auto-logout Off
Time until auto-logout 15.0min
Measured value display Primary values
Transformer name Transformer
Remote behavior Hardware and SCADA
USB interface Off
Service user access activation Activated
SNMP Agent Off
Home
Events
Information
Recorder
Settings
EN
CHANGE
REBOOT
Figure82: General
1. Go to Settings > Parameters > System > General.
2. Select the desired parameter.
3. Set the parameter.
4. Press the Accept button to save the modified parameter.
Commissioning wizard
You can use this parameter to set whether the commissioning wizard
[Section 7.6.4, Page 98] is to launch automatically when the device is
restarted.
Measured value display
You can use this parameter to set whether the displayed measured values
and control parameters are to refer to the primary side or secondary side of
the measuring transducers.
Display phase voltage
You can use this parameter to set whether the device is to display the phase
voltage (phase L-L (U1)) in the measured value display. If you activate this
parameter, the device uses the phase voltage as the measured value for
voltage regulation.
Transformer name
You can use this parameter to enter a transformer name for identification
purposes. The transformer name will be displayed on the main screen in the
visualization.