14 Technical data
Maschinenfabrik Reinhausen GmbH 2020384 6385142/08 ENETOS
®
ED
k1
k2
k3
l1
l2
l3
RDY
N L1 L2 L3
UI 3
55 mm (2.17 in)
ca. 120 mm (4.72 in)
119 mm (4.69 in)
54 mm (2.12 in)
Figure265: UI1 und UI3 dimensions
14.5.4 UI 5-4 voltage measurement and current measurement
UI5-4
Measurement 3-phase
Voltage measurement U
N
(RMS): 230V AC
Measuring range (RMS): 10...300VAC
Measuring accuracy (at U
N
, -25...+70 °C): < ±0.3%
Intrinsic consumption: <1VA
Measurement categoryIII in accordance with
IEC61010-2-30
Current measurement I
N
: 5A
Measuring range: 10mA...15A
Overload capacity: 15A (continuous), 100A (for 1s)
Measuring accuracy (at I
N
, -25...+70 °C): <± 0.5%
Intrinsic consumption: <1VA
Phase angle Measuring accuracy (-25 to +70 °C): V
x
/I
x
<±0.6°; V
x
/
U
y
<±0.15°
Frequency measurement f
N
: 50 / 60Hz
Measuring range: 35...75Hz
Measuring accuracy: (-25 to +70°C): <±0.002Hz
Table145: Technical data of the UI5-4 assemblies