9 Visualization
Maschinenfabrik Reinhausen GmbH 2020298 6385142/08 ENETOS
®
ED
9.31.1 Setting operator interval for OLTC maintenance
You can define the maintenance interval of your choice for the on-load tap-
changer. You can define the maintenance interval as dependent on time
and/or number of tap-change operations. If the limit is reached (100%), the
device triggers an event message (red).
Parameters
Maintena...tor
Interval type Deactivated
Number of tap-change operations 150000
Duration 1.0a
Date of next maintenance 17.09.2066 23:59:21
Event (yellow) 90.0%
Home
Events
Information
Recorder
Settings
EN
CHANGE
REBOOT
Figure224: Maintenance: OLTC operator
1. Go to Settings > Parameters > On-load tap-changer > Maintenance:
OLTC operator.
2. Select the desired parameter.
3. Set the desired parameter.
4. Press the Accept button to save the modified parameter.