14 Technical data
Maschinenfabrik Reinhausen GmbH 2020394 6385142/08 ENETOS
®
ED
MC 2-2
+
-
24V DC
+
-
24V DC
ETH12
ETH22
ETH11
ETH21
93 mm (3.66 in)
ca. 150 mm (5.9 in)
119 mm (4.69 in)
54 mm (2.12 in)
Figure273: MC2-2 and SW3-3 dimensions
14.5.10 Ambient conditions
Operating temperature -25...+70°C
Storage temperature -40...+85°C
Relative humidity 10...95% non-condensing
Air pressure Corresponds to 2000m above sea levelCorresponds to
2000m above sea level
Minimum spacing to other
devices/control cabinet
Top/Bottom: 88.9 mm (3.5 in; corresponds to 2 RU),
back 30 mm (1.2 in)
Table166: Permissible ambient conditions
14.5.11 Standards and directives
Electrical safety
IEC 61010-1
IEC 61010-2-030
Safety requirements for electrical measurement and con-
trol and regulation equipment and laboratory instruments
Protection class 1
Overvoltage category III
Contamination level 2
IEC 60950-1 Information technology equipment – Safety
Table167: Electrical safety