9 Visualization
Maschinenfabrik Reinhausen GmbH 2020282 6385142/08 ENETOS
®
ED
Go to Information > Active part > DGA > Dörnenburg.
9.27.2.7 IEC 60599 analysis
The display of the IEC60599 analysis shows the following information:
3D diagram, with the allocation of the last 10 measured values in the ar-
eas of the various error types.
Latest measured value: Darkest area with a display of the measure-
ment error.
Earliest measured value: Lightest area
Display of the error types. The error type of the latest measured value is
highlighted in white.
Proportion of the gas concentrations of the latest measured value
If you call up the visualization using a PC, the proportions of the gas concen-
trations and the time of the measurement are displayed for each measured
value via tooltip. Furthermore, you can rotate the diagram using the mouse.
Figure208: Display of the IEC60599 analysis
Go to Information > Active part > DGA > IEC60599.
9.28 MR sensor bus
The optionally available MR sensor bus function lets you connect digital and
analog sensors to the device over Modbus RTU. The MR sensor bus sup-
ports the connection of up to 31 sensors (Modbus slaves). The ISM® device
operates as the Modbus master.
Ensure that no other Modbus master is connected over the MR sensor bus.
Assign a unique Modbus address to each sensor you are connecting over
MR sensor bus. The MR sensor bus may experience errors if multiple sen-
sors are using the same Modbus address.