14 Technical data
Maschinenfabrik Reinhausen GmbH 2020 3736385142/08 EN ETOS
®
ED
14 Technical data
14.1 Motor-drive unit
The technical data applies to the standard design and may vary depending
on the design delivered. Subject to change without prior notice.
Motor power 0.75kW 2.0 kW 2.2kW
Motor circuit power supply 3AC/N 230/400V
Current Approx. 1.9A Approx. 5.2A Approx. 6.2A
Frequency 50Hz
Synchronous speed 1,500rpm
Rotations of the drive shaft per tap-change
operation
16.5
Duration of the tap-change operation Approx. 5.4s
Rated torque on the drive shaft 45Nm 90Nm 125Nm
Rotations of the hand crank per tap-change
operation
33 54
Maximum number of operating positions 35
Voltage supply for control circuit and heater
circuit
AC230V
Power consumption of the control circuit
(control/operation)
100VA / 25VA
Load capacity of micro-switches Switching capacity: 100W
AC voltage/current: 250V AC 100mA…4A
DC voltage/current: 220V DC 10mA…250mA
Degree of protection IP66 in accordance with DINEN60529
Test voltage to ground 2kV / 60s
Table136: ETOS® ED technical data
14.2 Control cabinet
Control cabinet ETOS® ED L
ETOS® ED L-S
ETOS®EDXL
Dimensions (width x height
x depth)
710 x 1368.4 x 464mm 710 x 1876.4 x 464mm
Power consumption
1
max. 14A
Voltage supply
1
3AC/N
380 to 440V
Frequency
1
50Hz or 60Hz
Control and heating circuit
voltage supply
220...240VAC

Table of Contents