4-18 Power-Up and Testing
To check Conveyor upstream and downstream SMEMA communication:
1. Perform a Service Shutdown as specified in the 2.11 Service Shutdown.
2. Attach the TS-01 upstream and downstream cable adapters to the TS-01 I/O Test Box.
3. Attach the TS-01 upstream and downstream cables to the appropriate SMEMA connectors at
the rear of the dispensing system (
Figure 4-12).
Figure 4-12 SMEMA Connections
4. Make sure that all of the IO/INDEP switches along the edge of the TS-01 I/O Test Box are
all set to
INDEP.
5. Start the dispensing system as described in
4.5 Powering on the Dispensing System.
6. Make sure that the
DRIVERS/OPTO I/O switch in the corner of the TS-01 I/O Test Box is set
to
OPTO I/O.
7. In the FmXP Main Window, click on
Configuration and then select Setup Conveyors.
8. Click on
I/O Test and then on the Outputs 0-31 tab (Figure 4-13).
9. Locate the upstream and downstream bits. Perform the actions specified in
Table 4-1.