EasyManuals Logo

Omron CQM1H - PROGRAM User Manual

Omron CQM1H - PROGRAM
602 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #126 background imageLoading...
Page #126 background image
101
Pulse I/O Board Section 2-2
Starting and Stopping Comparison
1,2,3... 1. Use CTBL(63) to save the comparison table in the CQM1H and begin com-
parisons.
If C is set to 000, then comparisons will be made using the target value
method; if 001, they will be made using the range comparison method. In
both cases the comparisons will begin after the comparison table is regis-
tered. While comparisons are being performed, high-speed counter 1 and
2 interrupts will be executed according to the comparison table. Refer to
the explanation of CTBL(63) in SECTION 5 Instruction Set for details on
the contents of the comparison tables that are saved.
Note Although setting the value of C to 002 registers a target value com-
parison table, and setting C to 003 registers a range comparison ta-
ble, comparison does not start automatically. In these cases, INI(61)
must be used to start the comparison operation.
2. To stop comparisons, execute INI(61) as shown below. Specify port 1 or 2
in P (P=001 or 002).
Note 1. To restart comparisons, set the first operand to the port number, and the
second operand to “000” (execute comparison), and execute the INI(61) in-
struction.
2. A table that has been registered will be retained in the CQM1H during op-
eration (i.e., during program execution) until a new table is registered.
Reading the PV of High-speed Counters 1 and 2
The following two methods can be used to read the PVs of high-speed
counters 1 and 2:
Reading the PV from memory
Using PRV(62)
Reading the PV from Memory
The PVs of high-speed counters 1 and 4 are stored in the corresponding data
area words in the following way.
Note These words are refreshed only once every cycle, so they may differ from the
actual PV.
(@)CTBL(63)
P
C
TB
P: Port
001: Port 1
002: Port 2
C: Mode
000: Target value table registered and comparison begun
001: Range table registered and comparison begun
002: Target table registered only
003: Range table registered only
TB: Beginning word of comparison table
(@)INI(61)
P
001
000
P: Port
001: Port 1
002: Port 2
Leftmost four digits Rightmost four digits Linear Mode Ring Mode
IR 233
IR 232 F8388608 to 08388607
(8,388,608 to 8,388,607)
(The leftmost digit becomes F when the number is
negative.)
00000000 to 00064999Port 1:
IR 235 IR 234
Port 2:

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron CQM1H - PROGRAM and is the answer not in the manual?

Omron CQM1H - PROGRAM Specifications

General IconGeneral
I/O CapacityUp to 512 points
Power Supply100 to 240 VAC, 50/60 Hz or 24 VDC (depending on model)
Instruction SetBasic and advanced instructions
Operating Temperature0 to 55°C
Program Capacity7.2K to 15.2K steps
Communication PortsRS-232C
Expansion SlotsUp to 3 expansion units
TypeProgrammable Logic Controller (PLC)
CPU TypeRISC
Program Memory7.2K to 15.2K steps
I/O Points512 max
Expansion CapabilityUp to 3 expansion units
Data MemoryRAM (battery backup)

Related product manuals