133
Operation Level Section 7-3
7-3-9 Alarm Upper Limit Value 2 (al2h)
Alarm Lower Limit Alarm Value 2 (al2l)
Condition: Alarm 2 type must be set to upper and lower limits, upper and
lower limit range, or upper and lower limit alarm with standby sequence.
These parameters independently set the upper and lower limit alarm values
when the mode for setting the upper and lower limits is selected for alarm 2
type.
Function • These parameters set the upper and lower limits of alarm 2.
• The decimal point position is dependent on the currently selected sensor.
For analog input, it is dependent on the “decimal point position” setting.
Communications
Settings
See Also
• Related Parameters
“Input type” “Alarm 2 type” (initial setting level) (page 147)
“Standby sequence reset method” (advanced function setting level)
(page 156)
“Alarm 2 open in alarm” (advanced function setting level) (page 157)
“Alarm 2 hysteresis” (advanced function setting level) (page 158)
7-3-10 MV Monitor for Heating (o)
Function During standard control, the MV is monitored, and during heating/cooling con-
trol, the MV on the heating side is monitored.
Communications
Monitoring
Setting ch Variable type Address
Alarm upper limit value 2 1 C1 0008
2 C1 0108
Alarm lower limit value 2 1 C1 0009
2 C1 0109
Setting range Unit Default
FFFFF831H to 00000270FH (−1999 to 9999) EU 0
ch Variable type Address
1C0 0004
2C0 0104
Control Monitoring range Unit
Standard FFFFFFCEH to 0000041AH (−5.0 to 105.0) %
Heating and cooling 00000000H to 0000041AH (0.0 to 105.0) %