154
Advanced Function Setting Level Section 7-6
7-6 Advanced Function Setting Level
7-6-1 Parameter Initialize (init)
Function This parameter initializes all settings to their defaults.
Communications Use the “parameter initialize” operation command. Refer to page 86 for infor-
mation.
Example of Use ON (on): Initializes all parameters.
OFF (off): Turns OFF the E5ZN after returning parameter settings to their
defaults.
7-6-2 Number of Multi-SP Uses (eU-m)
Function This parameter sets the multi-SP SPs that are used for the event input.
When the number of multi-SP uses setting has been changed, the setting
must enabled by executing a software reset or by turning ON the power
again.
Communications
Settings
7-6-3 Event Input Allocation (eU)
Condition: The number of multi-SP uses must be set to “0.
Function By selecting this parameter to “RUN/STOP,” an external signal can be
used to control RUN/STOP status.
Settings are not possible when the “number of multi-SP uses” parameter
is set to 1 (2: multi-SP).
Setting changes to event input allocations must be enabled by executing
a software reset or turning ON the power again.
Communications
ch Variable type Address
Shared C3 0017 or 0117
Setting range Unit Default
00000000H to 00000001H
0: No multi-SP
1: SP0/1
-0: No
multi-SP
ch Variable type Address
Shared C3 0018 or 0118