146
Initial Setting Level Section 7-5
Settings
See Also
• Related Parameters
“Manual reset” “Heating hysteresis” “Cooling hysteresis” (adjustment
level) (page 141)
7-5-6 Heating Control Period (cp)
Cooling Control Period (c-cp)
Condition: The control must be set to 2-PID control when the cooling side
control period is cooling/heating control.
Function • These parameters set the control periods. Set the control periods taking
the control characteristics and the electrical life expectancy of the relay
into consideration.
• In a standard control system, use the “heating control period” parameter.
• In a heating and cooling control system, the control period can be set
independently for heating and cooling.
Communications
Settings
See Also
• Related Parameter
“
PID/OnOff” (initial setting level) (page 145)
7-5-7 Direct/Reverse Operation (oreU)
Function Direct operation increases the MV when the PV increases. Alternatively,
reverse operation increases the manipulated variable when the PV
decreases.
Communications
Settings range Unit Default
00000000H to00000001H
0: ON/OFF (onof)
1: 2-PID (pid)
-1: 2-PID
Setting ch Variable type Address
Heating control period 1 C3 0008
2 C3 0108
Cooling control period 1 C3 0009
2 C3 0109
Setting Settings range Unit Default
Heating control
period
00000001H to 00000063H (1 to 99) Second 2
Cooling control
period
00000001H to 00000063H (1 to 99) Second 2
ch Variable type Address
1C3 000A
2C3 010A