85
Commands and Responses Section 5-9
5-9-16 Auto/Manual
Command
This command selects automatic/manual operation. It can be used when the
“PID/OnOff parameter is set to PID.
This command can be used in either setting area 0 or 1.
Before executing the command, use an operation command to enable com-
munications writing.
Note These variations of the command are supported by upgraded pulse output models and
analog output models only.
Response
Response code: The code shown above represents normal completion. For
details on the response code, refer to
5-7 Operation Commands.
5-9-17 PV Hold
Command
This command saves the PV when the command was executed in the variable
area.
This command can be used for setting area 0. If it is used in setting area 1, an
operation error will be returned.
Before executing the command, use an operation command to enable com-
munications writing.
Response
Response code: The code shown above represents normal completion. For
details on the response code, refer to
5-7 Operation Commands.
Related
information
Contents
ch Operation mode
“00” 1 Auto
“01” Manual
“10” 2 Auto
“11” Manual
“F0” 1, 2 Auto (See note.)
“F1” Manual (See note.)
MRC
“30” “05”
SRC
Command
code
Related
information
“09”
MRC SRC
Response code
“30” 05” “0000”
MRC
“30” 05”
SRC
Command
code
Related
information
“0A”
“00” or “10”
MRC SRC
Response code
“30” 05” “0000”