158
Advanced Function Setting Level Section 7-6
See Also Related Parameters
“Alarm value 1 to 3” (operation level) (page 131)
“Upper limit alarm value 1” “Lower limit alarm value 1” (operation level)
(page 132) “Upper limit alarm value 2” “Lower limit alarm value 2” (opera-
tion level) (page 132)
“Alarm 1 to 3 type” (initial setting level) (page 147)
“Control output 1 allocation” “Control output 2 allocation” (initial setting
level) (page 147) “Auxiliary output 1 allocation” “Auxiliary output 2 alloca-
tion” (initial setting level) (page 148)
“Alarm 1 to 3 hysteresis” (advanced function setting level) (page 158)
“Standby sequence reset method” (advanced function setting level)
(page 156)
“Alarm 1 to 3 latch” (advanced function setting level) (page 163)
7-6-8 Alarm 1 Hysteresis (alh1)
Alarm 2 Hysteresis (alh2)
Alarm 3 Hysteresis (alh3)
Condition: The alarm type must be set to other than “no alarm.
Function These parameters set the hystereses of alarm outputs 1, 2, and 3.
Setting changes to “alarm 1 to 3 hysteresis” must be enabled by execut-
ing a software reset or by turning ON the power again.
Communications
Settings
See Also
Related Parameters
“Alarm value 1 to 2” (operation level) (page 131)
“Upper limit alarm value 1” “Lower limit alarm value 1” (operation level)
(page 132) “Upper limit alarm value 2” “Lower limit alarm value 2” (opera-
tion level) (page 133)
“Alarm 1 to 3 type” (initial setting level) (page 147)
“Control output 1 allocation” “Control output 2 allocation” (initial setting
level) (page 147) “Auxiliary output 1 allocation” “Auxiliary output 2 alloca-
tion” (initial setting level) (page 148)
“Alarm 1 to 3 open in alarm” (advanced function setting level) (page 157)
“Standby sequence reset method” (advanced function setting level)
(page 156)
“Alarm 1 to 3 latch” (advanced function setting level) (page 163)
Setting ch Variable type Address
Alarm 1 hysteresis 1 C3 001D
2 C3 011D
Alarm 2 hysteresis 1 C3 001F
2 C3 011F
Alarm 3 hysteresis 1 C3 0021
2 C3 0121
Setting Setting range Unit Default
Alarm 1 hysteresis
Alarm 2 hysteresis
Alarm 3 hysteresis
00000001H to 00000270H
(0.1 to 999.9)
Temperature
input: °C/°F
Analog input:
EU
0.2