71
Operation Commands Section 5-7
5-7 Operation Commands
To send an operation command to the Temperature Controller, set the items in
the command text as follows:
Command Command Text
E5ZN Command Codes
Item Description
MRC/SRC Specify the FINS-mini operation command (operation com-
mand service).
Command code Place a command code in this field.
Related information Place information related to the operation command in this
field.
Command
code
Command code Related information
“00” Communications
writing
“00” or “10”: OFF (disable)
“01” or “11”: ON (enable)
“01” RUN/STOP “00”: Run ch1
“01”: Stop ch1
“10”: Run ch2
“11”: Stop ch2
“F0”: Run ch1, ch2 (See note 1.)
”F1”: Stop ch1, ch2 (See note 1.)
“02” Multi-SP “00”: Select SP0 for ch1
“01”: Select SP1 for ch1
“10”: Select SP0 for ch2
“11”: Select SP1 for ch2
“F0”: Select SP0 for ch1, ch2 (See note 1.)
“F1”: Select SP1 for ch1, ch2 (See note 1.)
“03” AT execute/cancel “00”: Stop ch1 AT
“01”: Execute ch1 AT
“10”: Stop ch2 AT
“11”: Execute ch2 AT
“F0”: Stop ch1, ch2 AT (See note 1.)
“F1”: Execute ch1, ch2 AT (See note 1.)
“04” Write mode “00” or “10”: Backup
“01” or “11”: RAM
“05” RAM data save “00” or “10”
“06” Software reset ”00” or “10”
“07” Move to setting area 1 ”00” or “10”
“08” Move to protect level ”00” or “10”
“09” Auto/manual “00”: Auto for ch1
“01”: Manual for ch1
“10”: Auto for ch2
“11”: Manual for ch2
“F0”: Auto for ch1, ch2 (See note 1.)
“F1”: Manual for ch1, ch2 (See note 1.)
22
MRC SRC
Command
code
22 bytes
“30” “05”
Related
information