149
Initial Setting Level Section 7-5
Communications
Settings
7-5-12 Auxiliary Output 2 Allocation (sub2)
Function This parameter allocates the data to be output to the auxiliary output 2 termi-
nals (terminals 14 and 15.)
Communications
Settings
7-5-13 Auxiliary Output 3 Allocation (sub3)
Condition: Analog output models only
Function This parameter allocates the data to be output to the auxiliary output 3 termi-
nals (terminals 16 and 17.)
Communications
ch Variable type Address
Shared C3 0010 or 0110
Settings range Default
Analog output models
E5ZN-2C@F03@-FLK
Pulse output models
E5ZN-2Q@H03@-FLK
E5ZN-2T@H03@-FLK
00000000H (0) ch1 Heating control output ch1 Heating control output Analog output
models:
2: Alarm 1 and
sensor error
alarm OR output
for ch1
Pulse output
models:
2: Alarm 1 and
HB alarm OR
output for ch1
00000001H (1) Cooling control output Cooling control output
00000002H (2) Alarm 1 and sensor error alarm
OR output
Alarm 1 and HB alarm OR out-
put
00000003H (3) Alarm 2 output Alarm 2 output
00000004H (4) Alarm 3 output Alarm 3 output
00000005H (5) ch2 Heating control output ch2 Heating control output
00000006H (6) Cooling control output Cooling control output
00000007H (7) Alarm 1 and sensor error alarm
OR output
Alarm 1 and HB alarm OR out-
put
00000008H (8) Alarm 2 output Alarm 2 output
00000009H (9) Alarm 3 output Alarm 3 output
ch Variable type Address
Shared C3 0011 or 0111
Setting range Default
Refer to the table of setting
ranges for auxiliary output
1 allocation.
Analog output models:
7: Alarm 1 and sensor error alarm OR output for ch2
Pulse output models:
7: Alarm 1 and HB alarm OR output for ch2
ch Variable type Address
Shared C3 002F or 012F