162
Advanced Function Setting Level Section 7-6
7-6-15 Additional PV Display (pUad)
Function This parameter enables displaying only the PV. It is added to the top of
the operation level of the E5ZN-SDL Setting Display Unit. It is used to
give the option of displaying the PV and SP, or just the PV only.
Setting changes to “additional PV display” must be enabled by executing
a software reset or by turning ON the power again.
Communications
Settings
7-6-16 Additional Temperature Input Shift Value Display (isdp)
Function This parameter conceals the display of the temperature input shift value in
the E5ZN-SDL Setting Display Unit operation level. The input shift func-
tion is enabled even when this parameter is set to “no display.”
Setting changes to “temperature input shift value display/not display”
must be enabled by executing a software reset or by turning ON the
power again.
Communications
Settings
7-6-17 Temperature Input Shift Type (istp)
Condition:
Upgraded pulse output models and analog output models only
Function This parameter sets whether a one-point shift or a two-point shift is used
as the input shift method.
This function can be used with upgraded pulse output models and analog
output models only.
Communications
ch Variable type Address
Shared C3 0029 or 0129
Setting range Unit Default
00000000H to 00000001H
0: Not added (off)
1: Added (on)
- 0: Not added
ch Variable type Address
Shared C3 002A or 012A
Setting range Unit Default
00000000H to 00000001H
0: No display (off)
1: Display (on)
-0: No display
ch Variable type Address
Shared C3 003E or 013E