57
Manual Mode Section 4-9
Relationship with RUN/
STOP
• The E5ZN can switch between auto and manual modes during both RUN
(control operating) and STOP (control stopped).
• Even if the manual manipulated variable is set to STOP during output in
manual mode, the operation status will not change and the output of the
manual manipulated variable will continue. (Refer to the following dia-
gram.)
4-9-2 Manual Manipulated Variable
Use host communications to set the manual manipulated variable to output in
manual mode.
The following table shows the relationship between the manual manipulated
variable setting range and the actual output.
Standard Control
Heating/Cooling Control
Output (100%)
100%
To manual
mode,
using auto/
manual
switching
To STOP,
with RUN/
STOP
setting
To automatic
mode, using
auto/manual
switching
Changes to
STOP status.
Time
Manual
manipulated
variable setting
Analog output models
E5ZN-2C@F03@-FLK
Pulse output models
E5ZN-2Q@H03@-FLK
E5ZN-2T@H03@-FLK
Heating side control output
100.0% to 105.0% Outputs the value set to man-
ual manipulated variable.
100.0%
0.1% to 99.9% Outputs the value set to man-
ual manipulated variable.
−5.0% to 0.0% Outputs 0.0%
Manual
manipulated
variable
setting
Analog output models
E5ZN-2C@F03@-FLK
Pulse output models E5ZN-
2Q@H03@-FLK
E5ZN-2T@H03@-FLK
Heating side
control output
Cooling side
control output
Heating side
control output
Cooling side
control output
100.0% to
105.0%
Outputs the
value set to
manual manip-
ulated variable.
Outputs 0.0% Outputs 100% Outputs 0.0%
0.1% to 99.9% Outputs the
value set to
manual manip-
ulated variable.
0.0% Outputs 0.0% Outputs 0.0%
−0.1% to
−99.9%
Outputs the
value set to
manual manip-
ulated variable.
Outputs the
value set to
manual manip-
ulated variable.
−100.0% to
105.0%
Outputs 100%