152
Initial Setting Level Section 7-5
Settings
See Also
• Related Parameters
“Input type” (initial setting level) (page 143)
“Control output 1 allocation,” “Control output 2 allocation” (initial setting
level) (page 148)
“Auxiliary output 3 allocation,” “Auxiliary output 4 allocation” (initial setting
level) (page 149)
■ Setting Example 1: SP Transfer Output
Change the input type from the default to 1 (thermocouple: K, −20 to 500°C)
to automatically change the transfer output upper limit to 500.0, and the trans-
fer output lower limit to
−20.0. By setting the SP limit to 0.0 to 100.0°C, the
transfer output upper limit will change to 100.0 and the transfer output lower
limit will change to 0.0.
■ Setting Example 2: PV Transfer Output
The sensor input temperature range will be set to the default transfer output
upper and lower limits. For example, if the input type is set to 0 (thermocouple:
K,
−200 to 1300°C), the transfer output upper limit will be set to 1,300 and the
transfer output lower limit will be set to
−200.
7-5-17 Current Output Type (ot-1)
Voltage Output Type (ot-2)
Condition: Analog output models only
Function This parameter sets current output as the output type for control output 1 and
control output 2, and sets voltage output as the output type for auxiliary output
3 and auxiliary output 4.
Communications
Settings
Setting range Unit Default
FFFFF831H to 0000270FH
SP transfer output, ramp SP transfer output, and PV transfer
output: −1999 to 9999 or −199.9 to 999.9
Heating MV transfer output, cooling MV transfer output: -1999
to 9999
--
Parameter ch Variable type Address
Current output type Shared C3 0039 or 0139
Voltage output type Shared C3 003A or 013A
Parameter Data range Default
Current output type 00000000H(0): 4 to 20 mA
00000001H(1): 0 to 20 mA
0: 4 to 20 mA
Voltage output type 00000000H(0): 1 to 5 V
00000001H(1): 0 to 5 V
0: 1 to 5 V