EasyManua.ls Logo

Omron E5ZN - 5-9-21 Read Controller Status

Omron E5ZN
216 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
88
Commands and Responses Section 5-9
5-9-21 Read Controller Status
Command
This command reads the operation status of the Temperature Controller.
The command can be used regardless of what state the Temperature Control-
ler is in.
Response
Related Information
If the Temperature Controller is in setting area 1 when the command is
received, it returns a response with “unknown” related information.
Response Code
MRC
“06” “01”
SRC
Operation status Description
“00” Control operating for all channels (No errors in setting area 0,
executing RUN.)
“01” Control has stopped for one channel (Errors other than errors
in setting area 0, not executing RUN.)
Response
code
Error name Description
“1001” Command length over The command is too long.
“2203” Operation error An error occurs in EEPROM.
“0000” Normal completion The command is successfully executed.
MRC
“06” “01”
SRC
Related
information
“0000”
Response code
Operation
status
7 6 5 4 3 2 1 0 Bit position
00000
Status
Value of bit
01
Current exceeded
Current hold
Input error
Not
detected
Detected
Not
detected
Detected
Not
detected
Detected

Table of Contents