Adjustment Level Section 7-4
7-4-5 SP 0 (sp-0)
SP 1 (sp-1)
Condition: The “number of multi-SP uses” parameter must be set to
either 1 or 2, and the “multi-SP uses” parameter must be set to ON.
These parameters set the SPs when the multi-SP function is used.
Function The values set in these parameters can be selected.
• When the SP has been changed, the set value of these parameters cur-
rently set by multi-SP is linked and changed.
• The decimal point position is dependent on the selected sensor.
During analog input, the decimal point position is dependent on the setting of
the “decimal point position” parameter.
Communications
Settings
See Also
• Related Parameters
“Number of multi-SP uses” (advanced function setting level) (page 154)
“Event input allocation” “Multi-SP uses” (advanced function setting level)
(page 154)
“PV/SP” (operation level) (page 129)
“Input type” (initial setting level) (page 143)
7-4-6 Temperature Input Shift (ins)
Condition: Refer to the following table for details.
Sometimes an error between the SP and the actual temperature occurs. To
offset this, a value obtained by adding an input shift value to the input is dis-
played as the measurement value and used for control.
Conditions of Use
Setting ch Variable type Address
SP 0 1 C1 000D
2 C1 010D
SP 1 1 C1 000E
2 C1 010E
Setting range Unit Default
Lower SP limit to upper SP limit EU 0
Setting Temperature input shift value
Analog output models
E5ZN-2C@F03@-FLK
Pulse output models
E5ZN-2Q@H03@-FLK
E5ZN-2T@H03@-FLK
Temperature input
shift value
ON ON
Input type
Platinum-resistance thermometer or thermocouple
(analog input and infrared temperature sensors not
included)
Temperature input
shift type
One-point shift -