Advanced Function Setting Level Section 7-6
Communications
Settings
See Also
• Related Parameter
“HBA used” (advanced function setting level) (page 159)
7-6-12 α (alfa)
Condition: The control must be 2-PID control.
Function • Normally, use this parameter at its default.
• This parameter sets the 2-PID constant α.
• Setting changes to “α” must be enabled by executing a software reset or
by turning ON the power again.
Communications
Settings
See Also
• Related Parameter
“
PID/OnOff” (initial setting level) (page 145)
7-6-13 MV Upper Limit (ol-h)
MV Lower Limit (ol-l)
Condition: The control must be 2-PID control.
Function • The “MV upper limit” and “MV lower limit” parameters set the upper and
lower limits of the manipulated variable. When the manipulated variable
calculated by the E5ZN exceeds the upper or lower limit, the upper or
lower limit will be used as the output level.
•MV Upper Limit
The setting ranges during standard control and heating and control output
2 control are different.
The manipulated variable at the cooling side during heating and cooling
control is expressed as a negative value.
• MV Lower Limit
The setting ranges during standard control and heating and cooling con-
trol are different.
The manipulated variable at the cooling side during heating and cooling
control is expressed as a negative value.
• Setting changes to “MV upper and lower limit” must be enabled by exe-
cuting a software reset or by turning ON the power again.
ch Variable type Address
1C3 0024
2C3 0124
Setting range Unit Default
00000001H to 000001F4H (0.1 to 50.0) A 0.1
ch Variable type Address
Shared C3 0025 or 0125
Setting range Unit Default
00000000H to 00000064H (0.00 to 1.00) - 0.65