81
Commands and Responses Section 5-9
5-9-9 Multi-SP
Command
This command switches between SPs that have been set in advance for SP 0
and SP1.
“No. of multi-SP uses” must be set to 0 and “Use multi-SP” must be set to ON.
This command can be used for either setting area 0 or 1.
Note These variations of the command are supported by upgraded pulse output models and
analog output models only.
Response
Response code: The code shown above represents normal completion. For
details on the response code, refer to
5-7 Operation Commands.
5-9-10 AT Execute/Stop
Command
This command executes or stopped autotuning.
This command can be used in setting area 0 only. If it is used in setting area
1, an operation error will be returned. An operation error will also be returned
in the following cases.
• When the “RUN/STOP” parameter for the specified channel is set to
“STOP.”
• When ON/OFF control is being used.
Before executing the command, use an operation command to enable com-
munications writing.
Note These variations of the command are supported by upgraded pulse output models and
analog output models only.
Related
information
Contents
ch Selected SP
“00” 1 SP 0
“01” SP 1
”10” 2 SP 0
“11” SP 1
“F0” 1, 2 SP 0 (See note.)
“F1” SP 1 (See note.)
MRC
“30” “05”
SRC
Command
code
Related
information
“02”
MRC SRC
Response code
“30” “05” “0000”
Related
information
Contents
ch Instruction details
“00” 1 Stop
“01” Execute
”10” 2 Stop
“11” Execute
“F0” 1, 2 Stop (See note.)
“F1” Execute (See note.)
MRC
“30” “05”
SRC
Command
code
Related
information
“03”