22
Setting the Input Type Section 3-1
3-1 Setting the Input Type
Set the input type corresponding to the sensor used. The E5ZN specifications
support two types of inputs, platinum resistance thermometers and thermo-
couples. Refer to the following tables and set the correct value for the temper-
ature range and the sensor used.
3-1-1 Input Type
To set the input type to a K thermocouple from −20.0 to 500.0°C, use host
communications or the E5ZN-SDL Setting Display Unit to set 1 as the set
value for the input type.
List of Input Types
Note The ES1A for K160 to 260°C has been discontinued.
Type Input type Name Set Value Input Temperature Setup Range
Platinum resis-
tance thermome-
ter input
Platinum resis-
tance thermometer
Pt100
0 −200 to 850 °C or −300 to 1,500 °F
1 −199.9 to 500.0 °C or −199.9 to 900.0 °F
2 0.0 to 100.0 °C or 0.0 to 210.0 °F
JPt100 3 −199.9 to 500.0 °C or −199.9 to 900.0 °F
4 0.0 to 100.0 °C or 0.0 to 210.0 °F
Type Input type Name Set Value Input Temperature Setup Range
Thermocouple
input
Thermocouple K
0 −200 to 1,300 °C or −300 to 2,300 °F
1 −20.0 to 500.0 °C or 0.0 to 900.0 °F
J2−100 to 850 °C or −100 to 1500 °F
3 −20 to 400.0 °C or 0.0 to 750.0 °F
T4−200 to 400 °C or −300 to 700 °F
17 −199.9 to 400.0 °C or −199.9 to 700.0 °F
E 5 0 to 600 °C or 0 to 1,100 °F
L6−100 to 850 °C or −100 to 1,500 °F
U7−200 to 400 °C or −300 to 700 °F
18 −199.9 to 400.0 °C or −199.9 to 700.0 °F
N8−200 to 1,300 °C or −300 to 2,300 °F
R 9 0 to 1,700 °C or 0 to 3,000 °F
S 10 0 to 1,700 °C or 0 to 3,000 °F
B 11 100 to 1,800 °C or 300 to 3,200 °F
Infrared tempera-
ture sensor
ES1A
K10 to 70°C 12 0 to 90 °C or 0 to 190 °F
K60 to 120°C 13 0 to 120 °C or 0 to 240 °F
K115 to 165°C 14 0 to 165 °C or 0 to 320 °F
(K160 to 260°C) 15 0 to 260 °C or 0 to 500 °F
Analog input 0 to 50 mV 16 One of the following ranges depending on the
results of scaling:
−1,999 to 9,999 or −199.9 to 999.9