164
Advanced Function Setting Level Section 7-6
7-6-19 Input Error Output (sero)
Condition: The Alarm 1 must be allocated for control output or auxiliary
output. Analog output models only.
Function This parameter sets whether to output only the alarm 1 output or whether
to output an OR of the alarm 1 output and sensor error alarm output when
an alarm 1 output is allocated in control or auxiliary output.
When the sensor error alarm output is enabled
(on), alarm 1 for ch1 will
turn ON when a sensor error occurs in a ch1 input, and alarm 1 for ch2
will turn ON when a sensor error occurs in a ch2 input.
Set the input alarm output to OFF when moving to the initial setting level,
advanced function setting level, or communications setting level.
This parameter is supported by analog output models only.
Communications
Settings
See Also
Related Parameters
“Control Output 1 Allocation,” and “Control Output 2 Allocation” (initial setting
level) (page 148)
“Auxiliary Output 3 Allocation,” and “Auxiliary Output 4 Allocation (initial set-
ting level) (page 149)
7-6-20 Cold Junction Compensation Method (cjc)
Condition: Input type must be thermocouple or infrared temperature
sensor.
Function Specifies whether cold junction compensation is to be performed inter-
nally by the Controller or to be performed externally when the input type
set value is No. 0 to 15, 17 or 18.
The cold junction compensation external setting is valid when the temper-
ature difference is measured using two thermocouples or two ES1As.
Setting changes to “cold junction compensation method” must be enabled
by executing a software reset or by turning ON the power again.
Communications
Settings
ch Variable type Address
Shared C3 003D or 013D
Setting range Default
00000000H(0): Sensor error alarm output disabled (off)
00000001H(1): Sensor error alarm output enabled (on)
0: Sensor error alarm
output disabled
ch Variable type Address
Shared C3 002E or 012E
Setting range Unit Default
00000000H to 00000001H
0: External (off)
1: Internal (on)
- 1: Internally

Table of Contents