79
Commands and Responses Section 5-9
5-9-6 Multiple Writes of Setting Data
Command
Multiple setting data can be written with the execution of one command. Up to
3 values can be written, even if the addresses are not consecutive.
Refer to
5-10 Variable Area Map for information on specifying variable types
and addresses.
Setting area 1 setting data can be written in setting area 1 only. An error will
be returned if this command is executed for setting area 0.
Before executing the command, use an operation command to enable com-
munications writing.
To save the operation/adjustment level setting data to internal non-volatile
memory, use the “write mode” operation command to set the write mode to
“backup.” If it is not set to backup mode, the setting data will not be stored
when the power is turned OFF. Refer to
6-3 Setup Level Configuration and
Front Panel Keys
for details on the operation/adjustment level.
Response
Response code: The code shown above represents normal completion. For
details on the response code, refer to
5-6 Write to Variable Area.
MRC SRC
Variable
type Address
“01” “13” “00”
Data
Setting data
Bit
position
Variable
type
Address
“00”
Data
Setting data
Bit
position
Variable
type
Address Setting data
ch Description
“C1” “0000” to “0019” 1 Setting data for setting area 0
“0100” to “0119” 2
“C3” “0000” to “003E” 1 Setting data for setting area 1
“0100” to “013E” 2
“C5” “0000” 1 Setting data for setting area 0
“0100” 2
“C7” “0000” to “0001” 1 Setting data for setting area 1
“0100” to “0101” 2
MRC SRC
Response code
“01” “13” “0000”