90
Variable Area Map Section 5-10
5-10 Variable Area Map
The variable area of the Temperature Controller is mapped in terms of vari-
able types and addresses as described below.
Variable type C0: Read-only data for setting area 0, including PVs and sta-
tus
Variable type C1: Setting data for setting area 0
Variable type C3: Setting data for setting area 1
Variable type C5: Setting data for setting area 0
Variable type C7: Setting data for setting area 1
Allocations for each variable are listed below.
A dash (-) in the “ch” column indicates data that is used by both channels.
Note
1. This data is used by pulse output models only.
2. This data is used by analog output models only.
3. This data is used by upgraded pulse output models and analog output models only.
Variable
type
Address ch Monitor value Description
C0 0000 1 PV Temperature: According to specified range for each sensor.
Analog:
Scaling lower limit 5% FS to scaling upper limit + 5% FS
0001 Status Refer to page 91.
0002 Internal SP Lower limit of SP to upper limit of SP
0003 Heater current value
monitor
00000000H to 00000226H (0.0 to 55.0) (See note 1.)
0004 MV monitor for heating Standard: FFFFFFCEH to 0000041AH (5.0 to 105.0)
Heating/cooling: 00000000H to 0000041AH (0.0 to 105.0)
0005 MV monitor for cooling 00000000H to 0000041AH (0.0 to 105.0)
0006 PV hold value Temperature: According to specified range for each sensor
Analog:
Scaling lower limit 5% FS to scaling upper limit + 5% FS
Value stored in internal non-volatile memory (RAM) when the
“PV hold” operation command was executed.
0100 2 PV Temperature: According to specified range for each sensor
Analog:
Scaling lower limit 5% FS to scaling upper limit 5% + FS
0101 Status Refer to page 91.
0102 Internal SP Lower limit of SP to upper limit of SP
0103 Heater current value
monitor
00000000H to 00000226H (0.0 to 55.0) (See note 1.)
0104 MV monitor for heating Standard: FFFFFFCEH to 0000041AH (-5.0 to 105.0)
Heating/cooling: 00000000H to 0000041AH (0.0 to 105.0)
0105 MV monitor for cooling 00000000H to 0000041AH (0.0 to 105.0)
0106 PV hold value Temperature: According to specified range for each sensor
Analog:
Scaling lower limit 5% FS to scaling upper limit + 5% FS
Value stored in internal non-volatile memory (RAM) when the
“PV hold” operation command was executed.