Initial Setting Level Section 7-5
7-5-18 Sensor Error Indicator Used (sedu)
Condition:
Upgraded pulse output models and analog output models only
Function This parameter sets whether the error indicator (ERROR) on the front
panel of the E5ZN will light or not light when a sensor error is detected.
For the initial setting, when an input channel sensor is not connected dur-
ing operation, a sensor error is detected and the ERROR indicator will
light. The parameter can be set to always not light, so that the ERROR
indicator will not light when a sensor error is detected.
This parameter is supported by upgraded pulse output models and ana-
log output models only.
Communications
Settings
ch Variable type Address
Shared C3 003B or 013B
Setting range Default
00000000H(0): Indicator always not lit.
00000001H(1): Sensor error indicator lit (ch1 only)
00000002H(2): Sensor error indicator lit (ch2 only)
00000003H(3): Sensor error indicator lit (ch1 or ch2)
3: Sensor error indicator lit
(ch1 or ch2)