82
Commands and Responses Section 5-9
Response
Response code: The code shown above represents normal completion. For
details on the response code, refer to
5-7 Operation Commands.
5-9-11 Write Mode
Command
This command selects backup mode and RAM write mode.
Default is RAM write mode.
This command can be used in either setting area 0 or 1.
Before executing the command, use an operation command to enable com-
munications writing.
When switching from RAM write mode to backup mode, the operation/adjust-
ment level setting data is written to internal non-volatile memory. Refer to
6-3
Setup Level Configuration and Front Panel Keys
for information on operation/
adjustment level.
Response
Response code: The code shown above represents normal completion. For
details on the response code, refer to
5-7 Operation Commands.
MRC SRC
Response code
“30” “05” “0000”
Related
information
Contents
”00” or “10” Backup mode
”01” or “11” RAM write mode
Write mode Description
Backup mode When operation/adjustment level setting data write has been
performed via communications, the data is written to internal
non-volatile memory. Refer to 6-3 Setup Level Configuration
and Front Panel Keys for information on operation/adjustment
level.
RAM write mode When operation/adjustment level setting data write has been
performed via communications, the data is not written to inter-
nal non-volatile memory. However, if the data is changed
using the E5ZN-SDL Setting Display Unit key operations, it is
written to internal non-volatile memory. Refer to 6-3 Setup
Level Configuration and Front Panel Keys for information on
operation/adjustment level.
MRC
“30” “05”
SRC
Command
code
Related
information
“04”
MRC SRC
Response code
“30” “05” “0000”