Commands and Responses Section 5-9
5-9-4 Write Protect Level Setting Data
Command
This command writes protect level setting data. For details on protect levels,
refer to
6-3 Setup Level Configuration and Front Panel Keys.
This command can be used in setting area 0 only. If the Temperature Control-
ler is in setting area 1 when the command is received, it returns an error.
Before executing the command, use operation commands to enable writing
and to enter the protect level.
Response
Response code: The code shown above represents normal completion. For
details on the response code, refer to
5-6 Write to Variable Area.
MRC SRC
Variable
type Address
Bit
position
“01” “02” “00”
No. of
elements
Data
“C1” “0001” Protect level setting data
Address Setting data
“0000” Operation/adjustment protection
“0001” Initial setting/communications protec-
tion
“0002” Setting change protection
“0100” Operation/adjustment protection
“0101” Initial setting/communications protec-
tion
“0102” Setting change protection
MRC SRC
Response code
“01” “02” “0000”