129
Operation Level Section 7-3
7-3 Operation Level
7-3-1 PV
Condition: The “additional PV display” parameter must be set to ON.
Function The PV is displayed on the No.1 display, and nothing is displayed (blank) on
the No. 2 display.
Communications
Monitoring
The decimal point position is dependent on the selected sensor.
See Also Related Parameters
“Input type” (page 143)
“SP upper limit” “SP lower limit” (page 145)
7-3-2 PV/SP
Function The PV is displayed on the No.1 display, and the SP is displayed on the No. 2
display.
Communications
See Also
Refer to the PV parameter.
ch Variable type Address
1C0 0000
2C0 0100
Monitoring range Unit
PV Input range lower limit 10% FS to input range upper limit
+10%FS
Scaling lower limit 10% FS to scaling upper limit +10%FS
EU
Monitoring range Unit
PV Input range lower limit 10%FS to input range upper limit
+10%FS
Scaling lower limit 10%FS to scaling upper limit +10%FS
EU
Monitoring range Unit
SP SP lower limit to SP upper limit EU
Monitor value/parameter ch Variable type Address
PV 1 C0 0000
2 C0 0100
SP 1 C1 0003
2 C1 0103