Adjustment Level Section 7-4
7-4-10 Dead Band (c-db)
Condition: The control system must be heating and cooling control.
This parameter sets the output dead band width in a heating and cooling con-
trol system. A negative setting sets an overlap band.
Function This parameter sets an area in which the control output is 0 centering around
the SP in a heating and cooling control system.
Communications
Settings
7-4-11 Manual Reset Value (of-r)
Condition: The control must be standard control or 2-PID control. The
“integral time” parameter must be set to 0.
Function This parameter sets the required manipulated variable to remove offset during
stabilization of P or PD control.
Communications
Settings
See Also
Related Parameters
PID/OnOff” (initial setting level) (page 145)
“Integral time” (adjustment level) (page 139)
ch Variable type Address
1C1 0016
2C1 0116
Setting range Unit Default
FFFFF831H to 0000270FH (199.9 to 999.9) EU 0.0
ch Variable type Address
1C1 0017
2C1 0117
Monitoring range Unit Default
00000000H to 000003E8H (0.0 to 100.0) % 50.0