78
Commands and Responses Section 5-9
5-9-5 Write Setting Data
Command
This command writes setting data. If the number of elements is set between
“2” and “6”, consecutive address setting data can be written.
For details on addressing, refer to
5-10 Variable Area Map.
This command can be used in setting area 1 only. If the Temperature Control-
ler is in setting area 0 when the command is received, it returns an error.
Before executing the command, use operation commands to enable commu-
nications writing.
To save the operation/adjustment level setting data to internal non-volatile
memory, use the “write mode” operation command to set the write mode to
“backup.” If it is not set to backup mode, the setting data will not be stored
when the power is turned OFF. Refer to
6-3 Setup Level Configuration and
Front Panel Keys
for details on the operation/adjustment level.
Response
Response code: The code shown above represents normal completion. For
details on the response code, refer to
5-6 Write to Variable Area.
MRC SRC
Variable
type Address
Bit
position
“01” “02” “00”
No. of
elements
Data
“0001” Setting data (setting area 1)
Variable
type
Address Setting data
ch Description
“C1” “0000” to “0019” 1 Setting data for setting area 0
“0100” to “0119” 2
“C3” “0000” to “003E” 1 Setting data for setting area 1
“0100” to “013E” 2
“C5” “0000” 1 Setting data for setting area 0
“0100” 2
“C7” “0000” to “0001” 1 Setting data for setting area 1
“0100” to “0101” 2
MRC SRC
Response code
“01” 02” “0000”