Advanced Function Setting Level Section 7-6
Communications
Settings
See Also
• Related Parameters
“Input type” (initial setting level) (page 143)
“Scaling upper limit” “Scaling lower limit” “Decimal point” (initial setting
level) (page 144)
7-6-6 Standby Sequence Reset Method (rest)
Condition: The alarm 1 to 3 type must be set to an alarm with a standby
sequence.
Function • This parameter sets the conditions for enabling reset after the standby
sequence of the alarm has been canceled.
• Condition A:
Control started (including power ON) or change made in SP, alarm value
(upper/lower limit alarm value), or input shift value (upper/lower limit tem-
perature input shift value).
• Condition B:
Power ON
• The following example shows the reset action when the alarm type is
lower limit alarm with standby sequence.
• Setting changes to “standby sequence reset” must be enabled by execut-
ing a software reset or by turning ON the power again.
Communications
ch Variable type Address
1C3 001A
2C3 011A
Setting range Unit Default
00000000H to 00000271H (0 to 9999)
0: OFF
EU/min. 0: OFF
Alarm point
(after change)
Alarm point
Alarm output:
Condition A
Alarm output:
Condition B
SP change
Condition A only
Alarm hysteresis
Standby sequence
canceled point
Standby sequence
reset point
Condition A only
ch Variable type Address
Shared C3 001B or 011B