140
Adjustment Level Section 7-4
7-4-9 Cooling Coefficient (c-sc)
Condition: The control must be either heating and cooling control or 2-
PID control.
If the heating and cooling characteristics of the control target differ enough to
prevent satisfactory control characteristics from being obtained by the same
PID parameters, adjust the proportional band (P) on the cooling side by add-
ing the cooling coefficient to control cooling.
Function In heating and cooling control, cooling side P is calculated by the following for-
mula to set the cooling coefficient:
Cooling side P = Cooling coefficient
× P (proportional operation)
Communications
Settings
See Also
• Related Parameter
“Proportional band” (adjustment level) (page 139)
ch Variable type Address
1C1 0015
2C1 0115
Setting range Unit Default
00000001H to 0000270FH (0.01 to 99.99) None 1.00