161
Advanced Function Setting Level Section 7-6
Communications
Settings
See Also
Related Parameter
PID/OnOff” (initial setting level) (page 145)
7-6-14 Input Digital Filter (inf)
Function Sets the time constant of the input digital filter. The following figure shows
the effect on data after passing through the digital filter:
Setting changes to “input digital filter” must be enabled by executing a
software reset or by turning ON the power again.
Communications
Settings
Setting ch Variable type Address
MV upper limit 1 C3 0026
2 C3 0126
MV lower limit 1 C3 0027
2 C3 0127
Setting Setting range Unit Default
MV upper
limit
For Standard Control:
(MV lower limit + 1)H to 0000041AH
(MV lower limit + 0.1 to 105.0)
% 105.0
For Heating and Cooling Control:
00000000H to 0000041AH
(0.0 to 105.0)
% 105.0
MV lower
limit
For Standard Control:
FFFFFFCEH to (MV upper limit 1)H
(5.0 to MV upper limit 1)
%-5.0
For Heating and Cooling Control
FFFFFBE6H to 00000000H
(105.0 to 0.0)
% -105.0
PV before passing through filter
PV after passing through filter
0.63 A
A
Time constant
Input digital filter
ch Variable type Address
1C3 0028
2C3 0128
Setting range Unit Default
00000000H to 00000270H (0.0 to 999.9) Second 0.0